Megohm Meters for Preventive Maintenance and Breakdowns

Megohm meters (meggers) are electrical meters used to check the resistance and condition of the motor windings and the condition of the refrigeration and oil environment around the motor windings. A megger is nothing but a giant ohmmeter that creates a very large dc voltage (usually 500 volts dc) from its internal battery. The meter will read out in megohms (millions of ohms). Any motor winding or electrical coil can be checked with a megger. A megohmmeter’s main function is to detect weak motor winding insulation and to detect moisture accumulation and acid formations from the motor windings to ground before they can cause more damage to motor winding insulation.

When dealing with HVACR hermetic and semi-hermetic compressor motors, as contaminants in the refrigerant and oil mixture increases, the electrical resistance from the motor windings to ground will decrease. Because of this, regular preventative maintenance checks can be made with a megohm meter and can signal early motor winding breakdown from a contaminated system when accurate records are kept.

One probe of the megger is connected to one of the motor winding terminals, and the other probe to the shell of the compressor (ground). Note: Make sure metal is exposed at the shell of the compressor where the probe is attached so that the compressor’s shell paint is not acting as an insulator to ground. When a button is pushed and held on the megger, it will apply a high dc voltage between its probes and measure all electrical paths to ground. It is important to disconnect all wires from the compressor motor terminals when megging a compressor motor.

Also, read the instructions that come with the meter to determine what time interval to energize the megger when checking winding or coils. If possible, it is a good idea to run the motor for at least one hour, disconnect power, disconnect all electrical leads, and then quickly connect the megger to the motor. This will give a more meaningful comparison between readings for the same compressor on different days, because of the approximate same winding temperatures.

Good motor winding readings should have a resistance value of a minimum of 100 megohms relative to ground. In fact, good motor winding resistance should be between 100 megohms and infinity.

A “failed” motor with low ohm resistance indicates a grounded motor. Many times a trouble call will indicate blown fuses or a tripped breaker.

Because of the very high resistance of the motor winding insulation, a regular ohmmeter cannot be used in place of the megger. A regular ohm meter does not generate enough voltage from its internal battery to detect high resistance problems like deteriorated winding insulation, moisture, or other system contamination.

Listed below are some other important tips service technicians should know about the use of a megohm meter:

• Never use a megger if the motor windings are under a vacuum.

• Meggers can be used for other electrical devices other than electric motors.

• Always consult with the meter manufacturer or user’s manual for detailed instructions on megging other electrical devices like coils.

• Meggers are often used in preventive maintenance programs, especially before a contractor signs a preventive maintenance contract to determine condition of the electrical devices.

Tags: , , ,

HVAC Industry News

Can I Still Install a 13 SEER Unit?

There are three key questions to ask when considering installing a 13 SEER unit. Which region you are in? When was the 13 SEER system built? Was it a heat pump or straight AC? You can still install a 13 SEER unit anywhere in the U.S. if it was manufactured before Jan. 1, 2015. If … Read More »

Emerson Climate Technologies Announces The Release Of CopelandTM Brand Products For R404A/ R507A And R134a Refrigerant Alternatives

AACHEN (GERMANY), October 15, 2014 — Emerson Climate Technologies, a business of Emerson (NYSE: EMR), announces its ongoing investment in sustainable refrigerant alternatives in anticipation of European Union rules. Both the European Union and U.S. EPA have announced plans to transition new applications away from high global warming potential refrigerants (R404A/ R507A). F-gas Regulation 517/2014 … Read More »

New Air Conditioner Standards Would Rank as Biggest Energy Saver in U.S. DOE History

Proposed Standards Would Save Businesses Billions Washington, D.C.—The Department of Energy (DOE) proposed new efficiency standards today that would slash commercial rooftop air conditioner energy use by about 30%. The proposed standards would achieve the largest national energy savings of any standard ever issued by the U.S. Department of Energy. “DOE’s new standards are a … Read More »

EPA Warns Against Use of Refrigerant Substitutes That Pose Fire and Explosion Risk

WASHINGTON – The U.S. Environmental Protection Agency (EPA) is warning homeowners, propane manufacturers and sellers, home improvement contractors and air conditioning technicians of potential safety hazards related to the use of propane or other unapproved refrigerants in home air conditioning systems. EPA is currently investigating instances where propane has been marketed and used as a … Read More »

%d bloggers like this: